Our Heating & Cooling Choices

Going into the renovation process we had never chosen a heating and cooling system before. Our tilt-n-turn windows meant we couldn’t have window air conditioners. And when I initially thought through the HVAC choices I wasn’t really in favor of forced air since it tended to be expensive, dusty, and take up a lot of space.

We wound up going with with hot water radiators plus mini-splits. Some of the money we saved going with rads, we spent on expensive European radiators (Runtal). We also didn’t go overboard on a zoned system with lots of thermostats. Instead we opted for pretty simple Danfoss valves. The end result looks like this…

runtal radiator with danfoss valve

The exposed pipes will be painted white when it’s all done. Most of the radiators in the house are two units high – that one is in the rental bedroom wall and shorter than the rest – so to get the same BTUs we have everywhere else we had to go with the model that’s 3 units high.

That’s inherently a pretty low-tech solution – a valve and a radiator. It’s just the radiator looks better than most and the valve is thermostatic – so it’s based on temperature works better than regular radiator valves.

[Incidentally – avoid steam radiators – there’s no such thing as a high efficiency steam boiler. To get high efficiency you need hot water radiators, not steam radiators.]

Because there’s a valve on every radiator we sorta get a zoned system where every room is a zone. It won’t work quite as well as a real zoned system with thermostats for every zone, but it also cost a lot less. And if we stay on top of it, it will probably perform about as well as a more sophisticated system.

There will be one thermostat for the heating system. A friend’s post on Facebook turned me on to the Nest thermostat. If you haven’t checked it out, take some time and watch the promo videos on their site – it’s incredibly cool. I can’t wait to get one.

The one “problem” that we’ve realized is the issue of curtains. With radiators under all the windows – if we hang curtains all the way to the floor they’ll cover the radiators…

runtal radiators below windows

That’s a bit of a problem because the tilt-n-turn windows limit our window covering choices. They swing inwards, so putting blinds at the top of the window framing is sorta impossible. We were thinking of doing a lot of curtains, but now worry the radiators won’t work very well when the curtains are pulled.

One area where a forced air system might be better is air exchange. Since the house is well insulated, we may not have enough fresh air entering the house. That is easier to solve with a forced air system – you just incorporate a fresh air intake. But honestly I don’t think we’ll have much of a problem – 2 people in 3,000 sq. ft. shouldn’t be a problem.

We are happy that we have mini-splits and that they’re both heating and cooling. The house is warm enough down to about freezing. It maintains 50+ degrees when it’s in the high 30s outside. That means we probably won’t turn on the boiler until it gets down around freezing. If we just need to take the chill out of the air in a single room (or if our tenant wants it to be warmer than we do) we can use the mini-split.

The mini splits are a bit of an eyesore – we tried to hide them the best we could, but they’re still there hanging on the wall. I don’t think that will bother us too much. To us the visual noise of the mini split unit isn’t any worse than the soffits you often have with forced air systems. If you’re the type who doesn’t want to see a mini-split hanging on your wall there’s always the concealed models you can tuck inside a closet. Those have the advantage of being able to cool/heat two rooms (like a bedroom and an en-suite bathroom) – but the concealed models aren’t quite as efficient due to the ductwork.

One other thing to mention is that we have radiators at each end of the house, and since the bathrooms are in the center of the house we were worried they could get a little cold. We were worried they could get a bit cold, so we put under floor heating pads in each bathroom with programmable thermostats. It’s not very efficient heat, but it won’t be used all that often – so it should be fine.

UPDATE:

Some of the comments asked how the radiator piping was configured. Here’s a diagram to explain how it’s been done…

radiator heating diagram

The model numbers are Runtal unless except where they say Slant/Fin. Since we have exposed brick on one side, both pipes are actually on the same side of the building – right next to each other. There are also valves to bleed air from the system in key locations (such as at the top of each riser). Notice that each radiator / loop has a Danfoss valve on it, so we can (nearly) turn off the radiator in rooms and the other radiators will get more flow.

6 thoughts on “Our Heating & Cooling Choices

  1. What is your piping arrangement? Single, two-pipe, two-pipe reverse? Was this indicated by architect or engineer? Asking because we wanted the same as yours in our project, but it was messed up between architect, engineer contractor. Now we ended up with single pipe and not the fine control we hoped for….

    • Can you do single pipe on hot water? I thought that was only possible with steam? (Goes up as steam, comes down as condensation water).

      We have a supply and a return going up two corners of the building. The whole house is just “one zone” – so it goes off the boiler as one pipe that splits and goes to the two corners. Then the water circulates down the two returns and combine as they go back into the boiler.

  2. Hey Jay,

    Nope, no single pipe on hot water – either 2-pipe or 2-pipe reverse. Also, you will get a not insignificant radiant heat gain from your sealed-up fireplace.

    I have been meaning to ask you, I never saw mechanical drawings on your place in my quick peek. Do you have any mechanical ventilation (especially, hopefully, with a heat exchanger on it)? You’ve sealed-up you place nice and tight, without some ventilation I’m concerned you may not have sufficient fresh air.

    The place looks great. Keep the posts coming!

    Peter

    • Peter –

      After looking at the Wikipedia article on it, I still don’t understand how 2-pipe or 2-pipe reverse applies to a hot water based system. It seems to say that hot water systems are based on “water loops”. I’ve added the diagram into the blog post above – hopefully that will clarify things.

      Our fireplace doesn’t throw all that much heat. It’s a little disappointing in that respect. There was a forced air kit available, but it’s not legal in the US (only in Canada).

      And no, we don’t have a heat exchanger. It’s something I’ve wondered about. But we’re two people in 3,000 sq. ft. and Dan has a 10″ fan through the roof in his top floor studio that’s inevitably going to be a bit leaky. The renter may have more of an issue with fresh air. We’ll deal with it if it becomes an issue.

      Let me know if you want to come by sometime…